Mechanical
characteristics :
Metal Sheet
cabinet,
Dimension:
190 x 70 x 70 cm ( h. w. d)
Weight:
290 kg
Paint:
RAL7032 light grey (electro-static powder coated
painting)
Lifting eye
Identification plate outside of Cabinet
Cable entry
: bottom , with gland plate
Standard
tags for all of wires
Standard
label for all of components
Electrical
characteristics :
Nominal
input voltage:
220VDC
+15%,-10%
Convertor output :
Nominal
voltage (Un): 24VDC:
Nominal
current (In) :
200A
Voltage
regulation:
Static: 2%
Efficiency: > 82%
Over
load:
CURRENT
LIMITER 110%
Protections
Polarity
reversal of input DC voltage
DC soft
rise in the input of Inverter
Short
circuit (fast fuse protection)
Current
Limit protection on converter output.
Fast fuses
for power modules protection DC input
MCCB
(molded case circuit breaker) for DC input and
output
Low DC input (disconnect
input section from DC source)
DC input
high (disconnect input section from DC source)
Low /high
convertor output voltage
Environmental
Ambient
temperature:
Operating:
0 to +45 C (50 C optional)
Storage:
-25 to
80
C
Relative
humidity:
Operation:
from 20% to 80% no condensation.
Storage:
from 15% to 90% (in original packaging)
Acoustic
noise:
Typical less
than 55 db
Altitude:
Up to 2000m
Measurements
:
Output voltage
Output
current
Input
voltage
Input
Current
System
status indicators and alarms:
LED for
CONVERTOR OK
LED for
DC INPUT FAIL
LED for
DC OUTPUT HIGH
LED for
DC OUTPUT LOW
LED for
CURRENT LIMIT
LED for
EARTH FAULT
Switches
located on front panel:
ON/
OFF SWITCH
Lamp test
Remote
alarms
DC INPUT
FAIL
EARTH FAULT
CIONVERTOR
FAIL
(Separate
dry type contact for each of them)
|