Text Box: • Indication of Type
P   L   ---   
Nominal
 Capacity (Ah)
Long Life Single Cell
 POLARIT
 

 

 

General Features

Sealed Construction

POLARIT unique construction and sealing technique guarantees that no electrolyte leakage can occur from the terminals or case of any POLARIT battery.

This feature insures safe and efficient operation of POLARIT batteries in any position.

 POLARIT batteries are classified as "Non-Sailable" and will meet all requirements of the International Air Transportation Association.

Long Service Life, Float or Cyclic

The POLARIT VRLA battery has a long life in float or cyclic service.

The expected life of float service is 20 yeas @ 25ºC

Maintenance-Free Operation

During the expected float service life of POLARIT batteries, there is no need to check the specific gravity of the electrolyte, or add water. In fact, there is no provision for these maintenance functions.

Heavy Duty Grids

The heavy duty lead calcium alloy grids in POLARIT batteries provide an extra margin of performance and service life in both float and cyclic applications, even

in conditions of deep discharge

 

Positive plates & Negative Plates

Positive plates are made from a Lead-Calcium system.

Separators

The glass fiber separators in POLARIT VRLA batteries have high absorbability to acid. The high porosity of the separators retains adequate electrolyte for the reaction of active materials in the plates.

Safety Vents

The venting system, which operates at 1 psi to 6 psi (0.07- 0.43kg/cm2) is designed to release excess gas and keep the internal pressure within the optimum range of safety. At the same time, it protects the negative plates from contamination of oxygen in the air. Vents are 100% visually inspected during battery production.

Low Self Discharge

Because of the use of Lead Calcium grids alloy, POLARIT VRLA battery can be stored for long periods of time without recharge.

 

• Applications

- Communication equipment

- Power generation plants

- Telecommunication control equipment

- Alarm systems

- Emergency lighting systems

- Uninterruptible power supplies and stand-by

- Electric power systems

- power for computers

- Power station

 

- Medical equipment

- Nuclear power station

- Fire and security systems

- Solar powered and wind powered systems

- Control equipment

- Load leveling and storage equipment

- Stand-by electric power

- Marine equipment

 

 

• Technical Specifications

Internal Resistant

(mΩ)

Short   Circuit Current (A)

Dimension (mm/Kg [(±5%)])

CAPACITY (Ah) at 25ºC

NOMINAL VOLTAGE

TYPE

WEIGHT

TH

H

W

L

In 10Hr

EV=1.80

In 5Hr

EV=1.75

In 1Hr

EV=1.60

 

0.85

1250

6

211

206

72

170

100

95

67

2

PL100

0.8

2500

12.7

350

329

111

170

200

180

134

2

PL200

0.67

3500

14.5

350

329

111

170

250

225

168

2

PL250

0.55

4000

17.5

350

330

151

170

300

270

201

2

PL300

0.5

4500

19

350

328

150

170

350

329

230

2

PL350

0.47

5000

28

350

329

176

210

420

360

260

2

PL420

0.38

6000

28.5

350

330

170

240

500

450

330

2

PL500

0.3

7000

35

350

331

175

302

600

540

400

2

PL600

0.23

9000

50

350

330

175

410

800

720

520

2

PL800

0.19

10700

61.6

350

328

175

475

1000

900

660

2

PL1000

0.19

10700

63

651

621

188

321

1000

900

660

2

PL1000H

0.13

14000

94

375

343

350

400

1500

1350

1000

2

PL1500

0.13

14000

100.1

651

621

188

321

1500

1350

1000

2

PL1500H

0.1

17000

115

375

343

350

490

2000

1800

1320

2

PL2000

0.1

17000

129

651

621

320

328

2000

1800

1320

2

PL2000H

0.08

20000

171

375

343

350

712

3000

2700

2010

2

PL3000

0.08

20000

212

651

621

323

474

3000

2700

2010

2

PL3000H

 

• Charge and Discharge Conditions in 25ºC (77ºF)  

    Table 1                                                         Table 2                                                                Table 3

Max  Discharge  Current

Max  Charge  Current

TYPE

500

20

PL100

1000

40

PL200

1250

50

PL250

1500

60

PL300

1700

70

PL350

2100

84

PL420

2500

100

PL500

3000

120

PL600

3500

160

PL800

4000

200

PL1000

4500

300

PL1500

5500

400

PL2000

6000

600

PL3000

 

Temperature Compensation

Voltage

Status

-3.0  mv/ºC

2.23~ 2.28

(2.25V/25ºC)

Floating

-3.3  mv/ºC

2.25~ 2.30

(2. 28V/25ºC )

Standby Mode

-5.0  mv/ºC

2.40~ 2.50

(2.40V/25ºC )

Cycle Use

 

Operation Temperature Range

Status

-20 ~  60 º C

Discharge

-10 ~  60 º C

Charge

-20 ~  60 º C

Storage

 

Effect of Temperature on Battery Capacity

The nominal battery capacity is based on the temperature of 25 ºC. Above this temperature, the capacity increases marginally but it must be noted that the working battery should be kept within the temperature design limitations of the product.

 

Chart 1

Battery Temperature and efficacy on Capacity

 

Discharge

 

40ºC

35ºC

30ºC

25ºC

20ºC

15ºC

10ºC

5ºC

0ºC

-5ºC

-10ºC

1.22

1.15

1.07

1

0.93

0.85

0.78

0.71

0.65

0.58

0.52

10 min

1.14

1.09

1.05

1

0.95

0.90

0.85

0.80

0.74

0.69

0.64

1 Hour

1.08

1.06

1.03

1

0.97

0.93

0.90

0.86

0.82

0.79

0.75

10 Hour

 

 

 

 

 

 

 

 

 

 

 

 

• Constant Current Discharge (Amperes) at 25ºC to 1.8V/Cell:

Discharge Time

TYPE

10 Hr

8 Hr

5 Hr

3 Hr

2 Hr

1 Hr

30 min

20 min

10

11

16

24

33

52.5

73

92

PL 100

20

25

36

57

74

108

161

202

PL 200

25

28

41.5

64

83

134

190

240

PL 250

35

40.5

51.8

81

107

170

227

305

PL 300

30

34

60

96

119

191

279

345

PL 350

42

46.2

71

103

138

217

319

401

PL420

50

61

90

131

172

277

380

500

PL500

60

62.7

100.1

153

202

317

447

565

PL 600

80

86

131.7

207

270

425

599

752

PL 800

100

112

169

273

536

549

790

975

PL 1000

100

112

169

273

536

549

790

975

PL 1000H

150

169

254

394

509

808

1127

1401

PL 1500

150

169

254

394

509

808

1127

1401

PL 1500H

200

217

341

529

679

1051

1471

1877

PL 2000

200

217

341

529

679

1051

1471

1877

PL 2000H

300

329.2

507

801

1032

1621

2215

2812

PL 3000

300

329.2

507

801

1032

1621

2215

2812

PL 3000H

 

• Constant Power Discharge (watts) at 25ºC to 1.8V/Cell:

Discharge Time

TYPE

10 Hr

8 Hr

5 Hr

3 Hr

2 Hr

1 Hr

30 min

20 min

19

22

31

49

64

100

139

170

PL100

39

45.2

68

106

132

207

292

363

PL150

45.5

53

82

121

162.5

250

342

421

PL200

58

68.3

101

157

201

319

442

550

PL300

70

74.2

116

181

253

361

502

625

PL350

80

99

142

216

271

419

589

727

PL420

97

111.7

170

261

336

522

724

900

PL500

110.8

128

195

303

377

602

819

1018

PL600

150

180

261

408

514.5

803.2

1109

1361

PL800

195

227.8

346

519

625

1009

1421

1770

PL1000

195

227.8

346

519

625

1009

1421

1770

PL1000H

288

328

501

765

976

1492

2081

2540

PL1500

288

328

501

765

976

1492

2081

2540

PL1500H

369

447

668

1009

1300.5

2002

2789

3401

PL2000

369

447

668

1009

1300.5

2002

2789

3401

PL2000H

552

672

1012

1516

1961

3020

4180

5105

PL3000

552

672

1012

1516

1961

3020

4180

5105

PL3000H